High pressure fault 1 (Outdoor unit)
1.Outdoor unit LEV2 actuation failure -> Cooling.
2.Closed refrigerant service valve.
3.Short cycle on the outdoor unit.
4.Dirty heat exchanger of the outdoor unit.
5.Outdoor fan (including fan parts) failure, motor failure, or fan controller malfunction Rise in discharge temp.
6.Solenoid valve (SV1a) malfunction (The by-pass valve (SV1a) can not control rise in high pressure).
7.Thermistor failure (TH3, TH7).
8.Pressure sensor failure.
9.Failure of the thermistor input circuit and pressure sensor input circuit on the controller board.
10.Thermistor mounting problem (TH3, TH7).
11.Disconnected male connector on the pressure switch (63H1) or disconnected wire.
12.Voltage drop caused by unstable power supply voltage.
- 1)Check resistance : 0.25W 1kΩ LED : DC15V 20mA or more.
- 2)Confirm that the refrigerant service valve is fully open.
- 3)3-4.Check the outdoor units for problems and correct them,If any.
- 4)Check the fan on the outdoor unit.(252)
- 5)In case of SV1a (Bypass valve) This solenoid valve opens when powered (Relay ON).
- 6)6.1) At compressor start-up, the SV1a turns on for 4 minutes, and the operation can be checked by the self-diagnosis LED displayand the closing sound.
- 7)6.2) To check whether the valve is open or closed, check the change of the SV1a downstream piping temperature while the valve is being powered.Even when the valve is closed, high-temperature refrigerant flows inside the capillary next to the valve.
- 8)(Therefore, temperature of the downstream piping will not be low with the valve closed.)
- 9)Check thermistor resistance. (TH3, TH7)
- 10)7.1) TH3
- 11)Short detection:
- 12)110°C [230°F] and above (0.4 kΩ)
- 13)Open detection:
- 14)-40°C [-40°F] and below (130 kΩ)
- 15)7.2) TH7
- 16)Short detection:
- 17)110°C [230°F] and above (0.4 kΩ)
- 18)Open detection:
- 19)-40°C [-40°F] and below (130 kΩ)
- 20)The high pressure sensor consists of the circuit shown in the figure below. If DC 5V is applied between the red and the black wires, voltage corresponding to the pressure between the white and the black wires will be output, and the value of this
- 21)voltagewill be converted by the microcomputer. The output voltage is 0.071V per 0.098MPa [14psi].
- 22)Check the temperature and the pressure of the sensor with LED monitor.
- 23)10-11.Check the temperature and the pressure of the sensor with LED monitor.
- 24)Check the input voltage at the power supply terminal block (TB1).