Skip to main content

Drain pump fault.(Models with a drain sensor)

City Multi VRF System — Error Code

Back to results
2500

Drain pump fault.(Models with a drain sensor)

Category: City Multi VRF System
Primary Error Code
-
Primary Error Detail Code
-
Error Code Description
<p>Drain pump fault.(Models with a drain sensor)</p>
Searched Device
Indoor
Fault Point

1. Drain pump failure.

2. Drain water drainage problem.

2.1) Clogged drain pump.

2.2) Clogged drain piping.

3. Adhesion of water drops to the drain sensor.

3.1) Trickling of water along the lead wire.

3.2) Rippling of drain water caused by filter clogging.

4. Indoor unit control board failure.

4.1) Drain pump drive circuit failure.

4.2) Drain heater output circuit failure.

5. Items (1) through (4) above and an indoor unit electronic valve closure failure (leaky valve) occurred simultaneously.

How to Fix
  1. 1)Check for proper functioning of the drain pump.
  2. 2)Check for proper drainage.
  3. 3)1) Check for proper lead wire installation.
  4. 4)Check for clogged filter.
  5. 5)If the above item checks out OK, replace the indoor unit control board.
  6. 6)Check the solenoid valves on the indoor unit for leaks.
Additional Info
-
Remark
-

Still having issues?

Our service team is ready to help you resolve this error.