Skip to main content

Drain sensor submergence.

City Multi VRF System — Error Code

Back to results
2500

Drain sensor submergence.

Category: City Multi VRF System
Primary Error Code
-
Primary Error Detail Code
-
Error Code Description
<p>Drain sensor submergence.</p>
Searched Device
Indoor
Fault Point

1. Drain water drainage problem.

1.1) Clogged drain pump.

1.2) Clogged drain piping.

1.3) Backflow of drain water from other units.

2. Adhesion of water drops to the drain sensor.

2.1) Trickling of water along the lead wire.

2.2) Rippling of drain water caused by filter clogging.

3. Failure of the relay circuit for the solenoid valve.

4. Indoor unit control board failure.

4.1 Drain sensor circuit failure.

How to Fix
  1. 1)Check for proper drainage.
  2. 2)Check for proper lead wire installation.
  3. 3)Check for clogged filter.
  4. 4)Replace the relay.
  5. 5)If the above item checks out OK, replace the indoor unit control board.
Additional Info
-
Remark
-

Still having issues?

Our service team is ready to help you resolve this error.