2503
Drain sensor (Thd) fault.
Primary Error Code
-
Primary Error Detail Code
-
Error Code Description
<p>Drain sensor (Thd) fault.</p>
Searched Device
Indoor, Lossnay
Fault Point
1. Faulty connector (CN31) insertion.
2. Broken or semi-broken thermistor wire.
3. Thermistor failure.
4. Indoor unit control board (error detection circuit) failure.
How to Fix
- 1)Check for connector connection failure.
- 2)Reinsert the connector, restart the operation, and check for proper operation.
- 3)Check for a broken thermistor wire.
- 4)Check the resistance of the thermistor.
- 5)0°C[32 °F]:6.0 kΩ
- 6)10°C[50 °F]:3.9 kΩ
- 7)20°C[68°F]:2.6 kΩ
- 8)30°C[86°F]:1.8 kΩ
- 9)40°C[104 °F]:1.3 kΩ
- 10)Replace the indoor unit control board if the problem recurs when the unit is operated with the No.-1 and No.-2 pins on the drain sensor connector (CN31) being short-circuited.
- 11)If the above item checks out OK, there are no problems with the drain sensor.
- 12)Turn off the power and turn it back on.