Open phase.

City Multi VRF System — Error Code

Back to results
4102

Open phase.

Category: City Multi VRF System
Primary Error Code
4152
Primary Error Detail Code
-
Error Code Description
<p>Open phase.</p>
Searched Device
Outdoor
Fault Point

1. Power supply problem.

1.1) Open phase voltage of the power supply.

1.2) Power supply voltage drop.

2. Noise filter problem.

2.1) Coil problem.

2.2) Circuit board failure.

3. Wiring failure.

4. Blown fuse.

5. CT3 failure.

6. Control board failure.

How to Fix
  1. 1)Check the input voltage to the power supply terminal block TB1.
  2. 2)2.1) Check the coil connections.
  3. 3)2.2) Check for coil burnout.
  4. 4)2.3) Confirm that the voltage at the CN3 connector is 198 V or above.
  5. 5)Confirm that the voltage at the control board connector CNAC is 198 V or above.
  6. 6)(If the voltage is below 198V, check the wiring connection between the noise filter board CN3, noise filter board CN2 and control board CNAC. Confirm that the wiring between noise filter TB23 and INV board SC-L3 is put through CT3.)
  7. 7)Check for a blown fuse (F01) on the control board.
  8. 8)(If a blown fuse is found, check for a short-circuiting or earth fault of the actuator.)
  9. 9)Replace the inverter if this problem is detected after the compressor has gone into operation.
  10. 10)Replace the control board if none of the above is causing the problem.