Skip to main content

Power supply signal sync error.

City Multi VRF System — Error Code

Back to results
4115

Power supply signal sync error.

Category: City Multi VRF System
Primary Error Code
-
Primary Error Detail Code
-
Error Code Description
<p>Power supply signal sync error.</p>
Searched Device
Outdoor
Fault Point

1. Power supply error.

2. Noise filter problem

2.1) Coil problem.

2.2) Circuit board failure.

3. Faulty wiring.

4. Wiring failure

Between noise filter CN3 and noise filter CN2 and control board CNAC

5. Control board failure.

How to Fix
  1. 1)Check the voltage of the power supply terminal block (TB1).
  2. 2)Check the coil connections.
  3. 3)2.1) Check for coil burnout.
  4. 4)2.2) Confirm that the voltage at the CN3 connector is 198 V or above.
  5. 5)Check fuse F01 on the control board.
  6. 6)Confirm that the voltage at the control board connector CNAC is 198 V or above.
  7. 7)If none of the items described above is applicable, and if the trouble reappears even after
  8. 8)the power is switched on again, replace the control board.
Additional Info
-
Remark
-

Still having issues?

Our service team is ready to help you resolve this error.