Electric system not operate due to damper abnormality.

City Multi VRF System — Error Code

Back to results
4124

Electric system not operate due to damper abnormality.

Category: City Multi VRF System
Primary Error Code
-
Primary Error Detail Code
-
Error Code Description
<p>Electric system not operate due to damper abnormality.</p>
Searched Device
Indoor
Fault Point

The damper is not located at the designated position.

How to Fix
  1. 1)Check there is something that interferes the opening or closing movement of the damper.
  2. 2)If damper does not open or close, turn OFF the power supply and measure the resistance of
  3. 3)the damper lock motors (ML1,ML2) and the damper motor (MV2).
  4. 4)The resistance value is normal each. →Replace the indoor electronic control P.C. board.
  5. 5)The resistance value is not normal each. →Replace the motor that indicates the abnormal value.
  6. 6)If damper opens or closes, measure the voltage between CN1X1 (+) and (-) and the voltage
  7. 7)between CN1Y1 (+) and (-) during the damper open by pressing VANE CONTROL button.
  8. 8)There is not 0V DC between CN1X1 (+) and (-). →Replace the damper limit switch (open)
  9. 9)There is not 5V DC between CN1X1 (+) and (-). →Replace the damper limit switch (close)
  10. 10)If damper opens or closes and voltages in 3) are normal, measure the voltage between CN1X1 (+)     and (-) and the voltage between CN1Y1 (+) and (-) during the damper close by pressing VANE          CONTROL button.
  11. 11)There is not 5V DC between CN1X1 (+) and (-). →Replace the damper limit switch (open)
  12. 12)There is not 0V DC between CN1X1 (+) and (-). →Replace the damper limit switch (close)
  13. 13)There is 5V DC between CN1X1 (+) and (-) and 0V DC between CN1X1 (+) and (-). →Replace
  14. 14)the indoor electronic control
  15. 15)P.C. board.