Electric system not operate due to damper abnormality.
Primary Error Code
-
Primary Error Detail Code
-
Error Code Description
<p>Electric system not operate due to damper abnormality.</p>
Searched Device
Indoor
Fault Point
The damper is not located at the designated position.
How to Fix
- 1)Check there is something that interferes the opening or closing movement of the damper.
- 2)If damper does not open or close, turn OFF the power supply and measure the resistance of
- 3)the damper lock motors (ML1,ML2) and the damper motor (MV2).
- 4)The resistance value is normal each. →Replace the indoor electronic control P.C. board.
- 5)The resistance value is not normal each. →Replace the motor that indicates the abnormal value.
- 6)If damper opens or closes, measure the voltage between CN1X1 (+) and (-) and the voltage
- 7)between CN1Y1 (+) and (-) during the damper open by pressing VANE CONTROL button.
- 8)There is not 0V DC between CN1X1 (+) and (-). →Replace the damper limit switch (open)
- 9)There is not 5V DC between CN1X1 (+) and (-). →Replace the damper limit switch (close)
- 10)If damper opens or closes and voltages in 3) are normal, measure the voltage between CN1X1 (+) and (-) and the voltage between CN1Y1 (+) and (-) during the damper close by pressing VANE CONTROL button.
- 11)There is not 5V DC between CN1X1 (+) and (-). →Replace the damper limit switch (open)
- 12)There is not 0V DC between CN1X1 (+) and (-). →Replace the damper limit switch (close)
- 13)There is 5V DC between CN1X1 (+) and (-) and 0V DC between CN1X1 (+) and (-). →Replace
- 14)the indoor electronic control
- 15)P.C. board.
Additional Info
-
Remark
-