Abnormal bus voltage drop (Detail code 108).

City Multi VRF System — Error Code

Back to results
4220

Abnormal bus voltage drop (Detail code 108).

Category: City Multi VRF System
Primary Error Code
4320
Primary Error Detail Code
108
Error Code Description
<p>Abnormal bus voltage drop (Detail code 108).</p>
Searched Device
Outdoor
Fault Point

If Vdc 289V or less is detected during Inverter operation. (S/W detection)

How to Fix
  1. 1)Power supply environment
  2. 2)Find out if there was a (momentary) power failure.
  3. 3)Check whether the power voltage (Between L1 and L2, L2 and L3, and L1 and L3) is 342V
  4. 4)or less across all phases.
  5. 5)Voltage drop detected
  6. 6)4220
  7. 7)2.1) Check the voltage between the FT-P and FT-N terminals on the INV board while the inverter is stopped and if it is 420 V or above, check the following items.
  8. 8)2.1.1) Confirm on the LED monitor that the bus voltage is above 289V.
  9. 9)Replace the INV board if it is below 289 V.
  10. 10)2.1.2) Check the voltage at CN72 on the control board. →Go to (3).
  11. 11)2.1.3) Check the noise filter coil connections and for coil burnout.
  12. 12)2.1.4) Check the wiring connections between the following sections Between the noise filter                    board and INV board. Between the INV board and DCL.Replace 72C if no problems
  13. 13)are found.
  14. 14)2.1.5) Check the IGBT module resistance on the INV board.
  15. 15)2.2 Check the voltage between the FT-P and FT-N terminals on the INV board while the inverter is stopped and if it is less than 420 V, check the following items.
  16. 16)2.2.1) Check the coil connections and for coil burnout on the noise filter.
  17. 17)2.2.2) Check the wiring between the noise filter board and INV board.
  18. 18)2.2.3) Check the connection to SCP1 and SC-P2 on the INV board.
  19. 19)2.2.4) Check the in-rush current resistor value.
  20. 20)2.2.5) Check the 72C resistance value.
  21. 21)2.2.6) Check the DCL resistance value. Replace the INV board if no problems are found.
  22. 22)แผงวงจรควบคุมผิดปกติ
  23. 23)ตรวจสอบว่าได้จ่ายแรงดันไฟฟ้า 12VDC ไปที่ขั้วต่อ CN72 บนแผงวงจรควบคุม ขณะอินเวอร์เตอร์ทำงาน หากไม่ได้จ่ายแรงดันไฟฟ้าหรือค่าไม่ถูกต้อง ให้ตรวจสอบฟิวส์ F01 หากไม่พบความผิดปกติเกี่ยวกับฟิวส์ ให้เปลี่ยนแผงวงจรควบคุม
Additional Info
-
Remark
-

Still having issues?

Our service team is ready to help you resolve this error.