Skip to main content

Abnormal bus voltage rise (Detail code 109).

City Multi VRF System — Error Code

Back to results
4220

Abnormal bus voltage rise (Detail code 109).

Category: City Multi VRF System
Primary Error Code
4320
Primary Error Detail Code
109
Error Code Description
<p>Abnormal bus voltage rise (Detail code 109).</p>
Searched Device
Outdoor
Fault Point

If Vdc ≥ 830V is detected during inverter operation.

How to Fix
  1. 1)Different voltage connection
  2. 2)Check the power supply voltage on the power supply terminal block (TB1).
  3. 3)INV board failure
  4. 4)2.1) If the problem recurs, replace the INV board or fan board.
  5. 5)In the case of 4220: INV board.
  6. 6)In the case of 4225: Fan board.
  7. 7)In the case of 4226: Fan board. (Fan box side)
Additional Info
-
Remark
-

Still having issues?