4240
Overload protection.
Primary Error Code
4340
Primary Error Detail Code
-
Error Code Description
<p>Overload protection.</p>
Searched Device
Outdoor
Fault Point
If the output current of "(Iac) >Imax (Arms)" or "THHS > 100°C [212°F] " is continuously detected for 10 minutes or more during inverter operation.
Model P150 - P250: Imax =15 Arms.
Model P300 - P500: Imax =27 Arms.
How to Fix
- 1)Air passage blockage.
- 2)Check that the heat sink cooling air passage is not blocked.
- 3)Power supply environment. Power supply voltage is 342 V or above.
- 4)Inverter failure,
- 5)Compressor failure,
- 6)Check that the compressor has not overheated during operation.
- 7)→ Check the refrigerant circuit (oil return section).
- 8)The model selection switches (SW5-3 - 5-8) on the outdoor unit are set incorrectly.
- 9)Check the setting for the model selection switch on the outdoor unit (Dipswitches SW5-3 - 5-8 on the outdoor unit control board).