External device error

Lossnay Heat Recovery Ventilation — Green Light Blinking (Times)

Back to results
Outdoor: 8 times

External device error

Unit: Indoor Category: Lossnay Heat Recovery Ventilation
Unit Type
Indoor
Fault Point

When the TM3 ⑥,⑦ output setting switch (SW5-6) is ON, the following conditions are applied

・OA temperature is still -10°C or lower, 60 minutes after the output started

・OA temperature is 15°C or higher within 15 minutes after the output started

・OA temperature is 70°C or higher

How to Fix
  1. 1)When external devices are connected, check the external devices
  2. 2)When external devices are not connected, check the TM3 ⑥,⑦ output setting switch (SW5-6)