Remote controller communication error

Lossnay Heat Recovery Ventilation — Green Light Blinking (Times)

Back to results
Outdoor: 9 times

Remote controller communication error

Unit: Indoor Category: Lossnay Heat Recovery Ventilation
Unit Type
Indoor
Fault Point

1. No Lossnay unit is set to "Main"

2. Multiple transmission cable are wired using multi core cables

3. Transmission cable and power supply cable are to close

4. Transmission cable is not securely connected

5. The length of the transmission cable wiring is longer than specified (longer than 500 m)

How to Fix
  1. 1)Turn off the main power and set the Main/Sub selection switch (SW1)(set the first unit to "Main" and the second and following units to "Sub")
  2. 2)Using suitable cables, wire the transmission cables so that they are separated from one another
  3. 3)Wire the transmission cable at least 5 cm away from the power supply cable
  4. 4)Check the transmission cable connection
  5. 5)Check the length of the transmission cable wiring
Additional Info
-
Remark
-

Still having issues?

Our service team is ready to help you resolve this error.