Error Code Results (14 results)
| # | Error Code | Type | Description / Cause | Solution | Remark |
|---|---|---|---|---|---|
| 1 | 0900 | Remote Controller |
Lossnay trial operation Trial operation switch on the Lossnay circuit board (SW2-1) is set to ON |
Check the trial operation switch View details |
- |
| 2 | 3126 | Remote Controller |
External device error When the TM3 ⑥,⑦ output setting switch (SW5-6) is ON, the following conditions are applied |
1. When external devices are connected, check the external devices. 2. When external devices are not connected, check the TM3 ⑥,⑦ output setting switch (SW5-6) View details |
- |
| 3 | 3602 | Remote Controller |
Damper related error 1. Damper board operation is not correct |
1. Remove the rod, and check whether the damper board can be moved manually. 2. Check the connection of the lead wire connectors and the circuit connector. 3. Check the switch (SW5-10) setting. LGH-15 to 100 types : OFF. LGH-150 and 200 types : ON View details |
- |
| 4 | 4116 | Remote Controller |
Fan motor operation drive error 1. The Lossnay fan does not stop due to a breakdown of the fan motor operation drive of the circuit board |
1. Check and replace the circuit board. 2. Check and replace the fan motor View details |
*LGH-150 and 200 types do not display errors |
| 5 | 5101 | Remote Controller |
OA thermistor related error Connectors for the thermistor are not correctly connected |
Check the connection of the lead wire connectors and the circuit connectors View details |
- |
| 6 | 5102 | Remote Controller |
RA thermistor related error Connectors for the thermistor are not correctly connected |
Check the connection of the lead wire connectors and the circuit connectors View details |
- |
| 7 | 6600 | Remote Controller |
Multiple address error There is another unit with the same address setting |
Check the addresses of devices in the system View details |
when using M-NET |
| 8 | 6602 | Remote Controller |
Communication circuit section error 1. Controller where error originally occurred is defective |
1. Check the controller where the error occurred. 2. Replace the circuit board View details |
when using M-NET |
| 9 | 6603 | Remote Controller |
Transmission cable error 1. Power is not supplied to the same transmission cable from two or more power supply units |
Adjust the wiring of the power supply unit View details |
- |
| 10 | 6604 | Remote Controller |
Communication circuit section error 1. Controller where error originally occurred is defective |
1. Check the controller where the error occurred. 2. Replace the circuit board View details |
when using M-NET |
| 11 | 6607 | Remote Controller |
No ACK error 1. Power is not supplied to Lossnay |
1. Check the power supply to Lossnay. 2. Check the Lossnay address. 3. Using suitable cables, wire the transmission cables so that they are separated from one another. 4. Check the transmission cable connection. 5. Check the length of the transmission cable wiring View details |
when using M-NET |
| 12 | 6801 | Remote Controller |
PZ-60DR-E communication error 1. When using multiple Lossnay units, the Main/Sub setting has not been made for the second unit and following units |
1. Turn off the main power and set the Main/Sub selection switch (SW1)(set the first unit to "Main" and the second and following units to "Sub"). 2. Using suitable cables, wire the transmission cables so that they are separated from one another. 3. Wire the transmission cable at least 5 cm away from the power supply cable. 4. Check the transmission cable connection. 5. Check the length of the transmission cable wiring View details |
when using M-NET |
| 13 | 6202 | Remote Controller |
Remote controller error The remote controller has broken down |
Replace the remote controller View details |
when not using M-NET |
| 14 | 6608 | Remote Controller |
Lossnay communication error 1. When using multiple Lossnay units, the Main/Sub setting has not been made for the second unit and following units |
1. Turn off the main power supply and set the Main/Sub selection switch (SW1)(first unit to "Main", second and following units to "Sub"). 2. Using suitable cables, wire the transmission cables so that they are separated from one another. 3. Wire the transmission cable at least 5 cm away from the power supply cable. 4. Check the transmission cable connection. 5. Check the length of the transmission cable wiring View details |
when not using M-NET LC |
No matching error found
Try adjusting your search terms.
How to check error by yourself